Addressable 2 Loop Fire Alarm Panel

Features

Advanced microprocessor based
DIGITAL ADDRESSABLE fire alarm control panel.

  • 2 Loop digitally addressable zones.
  • Each zone support 99 addressable devices
  • Supports addressable MCP.
  • 32 character field programmable point text for each sensor
  • 40 x 2 Character LCD display.
  • Stand Alone models
  • Common soundercircuit.
  • Field programming through ATX keyboard.
  • All zone wiring circuitsare supervised.
  • Operates on 220v 50Hz Ac mains power.
  • 24V DC stand-by Supply.
  • Loop isolationfacility.
  • Loop wise fire, fault& isolation LED indication

Specifications

  • Primary Power: 220VAC, 60/50hz, 3Amps.
  • Standby Power: 24V DC (2 Nos of 12v, 7.2Ah (Max.) & (Built-in for 7.2Ah) Sealed Lead acid battery)
  • Operating Temperature – 0 – 49° C/32-120° F.
  • Relative Humidity 93 ± 2% RH non-condensing
  • Charging Voltage – 26V, ± 2% NominalCharging Current – 1.2A (Max.).
  • All zone are Class B Style B/C operation (Programmable). Normal Operating Voltage:18 – 24 VDC.
  • Alarm Current: 15 30mA.
  • Loop resistance: 180 ohms Maximum. End-Of-Line Resistor: 2K7, 1/2wattl
  • Standby Current: 7mA (2mA for Detectors)
  • Class B, Style – Y wiring
  • Common Two Form- C Relays
  • Relay contact Rating:2Amps @30 VDC, 0.5 Amps @ 125VAC (Resistive only). Power Factor:1.0
  • Programmable Input circuits
  • No of Zone: 2 Loop
  • Normal Operating Voltage:24 VDC.
  • Short Circuit Current: 3mA
  • Maximum. Loop resistance: 180 ohms Maximum.
  • Dimensions: 382mmx382mmx110m
  • Weight: 6.3kg without battery
  • Maximum No Devicesper zone: 99 devices in any combination (MCP, Detectors, Modules)